Analog Output Module

19

Publication 1771-IN044C-EN-P - October 2002

European Zone 2 Certification

This equipment is intended for use in potentially explosive atmospheres as defined by European

Union Directive 94/9/EC.
The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been

found to comply with the Essential Health and Safety Requirements relating to the design and

construction of Category 3 equipment intended for use in potentially explosive atmospheres,

given in Annex II to this Directive. The examination and test results are recorded in confidential

report No. 28 682 010.
Compliance with the Essential Health and Safety Requirements has been assured by

compliance with EN 50021 (1999).

IMPORTANT

Observe the following additional Zone 2 certification requirements:

This equipment is not resistant to sunlight or other sources of UV

radiation.

The secondary of a current transformer shall not be open-circuited when

applied in Class I, Zone 2 environments.

Equipment of lesser Enclosure Type Rating must be installed in an

enclosure providing at least IP54 protection when applied in Class I, Zone

2 environments.

This equipment shall be used within its specified ratings defined by

Allen-Bradley.

Provision shall be made to prevent the rated voltage from being exceeded

by transient disturbances of more than 40% when applied in Class I, Zone

2 environments.