Analog Output Module

6

Publication 1771-IN044C-EN-P - October 2002

Voltage Output Version of the Module

If you are using the voltage output version (1771-OFE1), you must
set several configuration jumpers on the module’s circuit board. You
must set these jumpers before you can proceed with configuring the
module. When you set these jumpers, you configure each channel for
one of the three voltage ranges listed above. The module is shipped
with the jumpers in the +10V position.

Set the Last State Configuration Jumpers

The LAST STATE configuration jumpers determine the value of all
the module’s outputs whenever communication between the module
and the processor is lost. This condition occurs when a processor or
adapter faults, or the processor is placed in the PROG or TEST
mode, or if the remote I/O cable breaks.
This is a significant safety feature. You can choose to have the
module’s outputs go to the minimum, middle or maximum of their
respective ranges or hold their last state if a module or system fault
occurs or if the system processor changes from RUN to PROG
mode.
You do this by placing the LAST STATE configuration jumpers on
eight (four jumpers on sets of pins) of the stake pins corresponding
to MIN, MID or MAX. If you do not place configuration jumpers in
one of these positions, the module defaults to the HOLD LAST
VALUE setting.

IMPORTANT

On power-up, the module’s output is

disabled until the module receives the first
block transfer write. The output then enables
with the value that you send it in the block
transfer write block.

We ship 1771-OFE modules with the LAST

STATE configuration jumpers in the MID
position.

!

ATTENTION

Switch 1 of the I/O rack affects the function of the
configuration settings as indicated in the table below.

Rack Switch 1

Configuration Jumper Setting

Setting

MIN

MID

MAX

HOLD LAST STATE

Last State

Last State

Last State Last State

Last State

Reset

Min

Mid

Max

Last State

Rack switch 1 determines what output conditions occur during a rack
fault.