Rockwell Automation 1771-OFE Analog Output Module Installation Instructions User Manual

Page 4

Advertising
background image

Analog Output Module

4

Publication 1771-IN044C-EN-P - October 2002

!

ATTENTION

Preventing Electrostatic Discharge

This equipment is sensitive to electrostatic

discharge, which can cause internal damage and

affect normal operation. Follow these guidelines

when you handle this equipment:

Touch a grounded object to discharge potential

static.

Wear an approved grounding wriststrap.

Do not touch connectors or pins on component

boards.

Do not touch circuit components inside the

equipment.

If available, use a static–safe workstation.

When not in use, keep modules in appropriate

static–safe packaging.

The 1771-OFE module can be used with any 1771 I/O chassis.
Compatibility and data table use is listed below.

C

Use of Data Table

Compatibility

Catalog

Number

Input

Image

Output

Image

Read

Block

Write

Block

Addressing

Chassis

S i

Image

Bits

Image

Bits

Block

Words

Block

Words 1/2ĆSlot

1ĆSlot

2ĆSlot

Series

1771ĆOFE/B

8

8

5

13

Y

Y

Y

A, B

A = Compatible with1771ĆA1, ĆA2, ĆA4

B = Compatible with1771ĆA1B, ĆA2B, ĆA3B, ĆA3B1, ĆA4B

Y = Compatible without restriction.

The analog output module receives its power through the 1771 I/O
chassis backplane from the chassis power supply. It does not require
any other external power supply. When planning your system, you
must consider the power usage of all modules in the I/O chassis to
prevent overloading the I/O chassis backplane and/or power supply.
Add this to the requirements of all other modules in the I/O chassis.

Analog Module

Power Requirement

1771ĆOFE1

1 5A @ 5V dc

1771ĆOFE2

1.5A @ 5V dc

1771ĆOFE3

2.5A @ 5V dc

Understand Product

Compatibility

Calculate Power

Requirements

Advertising