CompactBlock Distributed I/O on Remote I/O Series D 11
Publication
1791R-IN002B-EN-P - August 2003
Mount the Block(s)
The base and expansion modules mount to a panel or DIN rail which must be
grounded before installing the module(s).
Base Module Mounting
Install the CompactBlock base module on a panel or DIN rail.
DIP
Switch
No.
Description
ON
OFF
SW2
1
Comm Rate
00=57.6K
01=115.2K
10=230.4K
11=230.4K
2
Comm Rate
3
N/A
4
Hold Last State
Hold Last State Output Reset
5
Processor Restart/Lockout Lockout
Restart
6
Last I/O
Last Rack
Not Last Rack
7
Filter Speed Setting
00=2ms
10=4ms
01=8ms
11=16ms
8
Filter Speed Setting
!
WARNING
When used in a Class I, Division 2, hazardous
location, this equipment must be mounted in a suitable
enclosure with proper wiring method that complies
with the governing electrical codes.