Mount the block(s) – Rockwell Automation 1791R-XXXX CompactBlock Distributed I/O on Remote I/O Series D I.I. User Manual

Page 11

Advertising
background image

CompactBlock Distributed I/O on Remote I/O Series D 11

Publication

1791R-IN002B-EN-P - August 2003

Mount the Block(s)

The base and expansion modules mount to a panel or DIN rail which must be
grounded before installing the module(s).

Base Module Mounting

Install the CompactBlock base module on a panel or DIN rail.

DIP

Switch

No.

Description

ON

OFF

SW2

1

Comm Rate

00=57.6K

01=115.2K

10=230.4K

11=230.4K

2

Comm Rate

3

N/A

4

Hold Last State

Hold Last State Output Reset

5

Processor Restart/Lockout Lockout

Restart

6

Last I/O

Last Rack

Not Last Rack

7

Filter Speed Setting

00=2ms

10=4ms

01=8ms

11=16ms

8

Filter Speed Setting

!

WARNING

When used in a Class I, Division 2, hazardous
location, this equipment must be mounted in a suitable
enclosure with proper wiring method that complies
with the governing electrical codes.

Advertising