Maximum Output Data Format (Base Modules -8B8P or --8V8P)

Word

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Reserved

O7

O6

O5

O4

O3

O2

O1

O0

Base

1

Reserved

Analog Output Data Channel 0

2

Reserved

Analog Output Data Channel 1

3

OE

HLS

R

IF

IR3

IR2

IR1

IR0

IM3 IM2 IM1 IM0 OR1 OR0 OM1 OM0

4

Reserved

5

Reserved

OM x Output Mode Selection

Set “0”: Voltage Mode

Set “1”: Current Mode

OR x Output Range Selection on Current ModeSet “0”: 4-20mA

Set “1”: 0-20mA

IM x Input Channel Mode Select

Set “0”: Voltage Mode

Set “1”: Current Mode

IR x Input Range Select on Current Mode

Set “0”: 4-20mA

Set “1”: 0-20mA

IF

Input Filter Selection

Set “0”: 50Hz

Set “1”: 60Hz

R Reserved;

HLS HLS/OFF

Set “0”: Output Reset

Set “1”: Hold Last State

OE

Output Enable

Set “0”: Output Disabled

Set “1”: Output Enabled

(Output is 0mA at 0-20mA mode and 4-20mA mode

and 0V at 0-10V mode when this bit is 0)

Maximum Input Data Format (Base Modules -4B4P)

Bit Position

Word

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Reserved

In3

In2

In1

In0

Base

1

Reserved

Analog Input Data Channel 0

2

Reserved

Analog Input Data Channel 1

3

Reserved

Analog Input Data Channel 2

4

Reserved

Analog Input Data Channel 3

5

URo1 URo0 ORo1 ORo0 OW3 OW2 OW1 OW0 ORi3 ORi2 ORi1 ORi0 Reserved

RF

UF

UF

Module Unrecoverable Fault

Set “0”: No Error

Set “1”: Error

RF Module

Recoverable

Fault

Set

“0”: No Error

Set “1”: Error

ORi x Over Range Input Channel

Set “0”: No Over Range

Set “1”: Over Range

OW x Input Open Wire (@ 4-20mA Range)

Set “0”: No Open Wire

Set “1”: Open Wire

ORo x Output Data Over Range

Set “0”: No Over Range

Set “1”: Over Range

URo x Output Data Under Range (@4-20MA Range)Set “0”: No Under RangeSet “1”: Under Range