Troubleshoot with the Indicators

The 1791R I/O module has the following indicators:

• Status indicator - base only
• Comm indicator - base only
• I/O status indicators - base and expansion

Maximum Output Data Format (Base Modules -4B4P)

Word

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Reserved

O3

O2

O1

O0

Base

1

Reserved

Analog Output Data Channel 0

2

Reserved

Analog Output Data Channel 1

3

OE

HLS

R

IF

IR3

IR2

IR1

IR0

IM3 IM2 IM1 IM0 OR1 OR0 OM1 OM0

4

Reserved

5

Reserved

OM x Output Mode Selection

Set “0”: Voltage Mode

Set “1”: Current Mode

OR x Output Range Selection on Current ModeSet “0”: 4-20mA

Set “1”: 0-20mA

IM x Input Channel Mode Select

Set “0”: Voltage Mode

Set “1”: Current Mode

IR x Input Range Select on Current Mode

Set “0”: 4-20mA

Set “1”: 0-20mA

IF

Input Filter Selection

Set “0”: 50Hz

Set “1”: 60Hz

R Reserved;

HLS HLS/OFF

Set “0”: Output Reset

Set “1”: Hold Last State

OE

Output Enable

Set “0”: Output Disabled

Set “1”: Output Enabled

(Output is 0mA at 0-20mA mode and 4-20mA mode

and 0V at 0-10V mode when this bit is 0)

Status Indicator

Indication:

Status:

Off

No power

Red

Hardware or software error, power is low

Green

Normal operation

Flashing Red

Comm failure 1*

Flashing Red/Orange

Expansion error

*1 Comm fail = communication cable disconnected, 100ms between valid frames, no more than

255 valid frames between valid frames addressed to module, 20ms idle time exceeded.

**2 COMM and STATUS will alternately flash when processor restart lockout is selected, a

fault has occurred and the processor is communicating with the module.