Connect the input/output wires to the block, Stranded (cu) with 3/64 inch insulation – Rockwell Automation 1791R-XXXX CompactBlock Distributed I/O on Remote I/O Series D I.I. User Manual

Page 14

Advertising
background image

14 CompactBlock Distributed I/O on Remote I/O Series D

Publication

1791R-IN002B-EN-P - August 2003

4. Plug the expansion cable into both the base and expansion modules.

5. Replace the expansion covers on both modules.

Connect the Input/Output Wires to the Block

Two sets of VDC+ and GND power pins are located on each terminal (one
for each bank of 8 points) except on the 1791R-4B4P module. The following
figures show the wiring information for both sinking and sourcing wiring.
Input and Output wiring use up to 14AWG (2mm

2

) stranded (Cu) with 3/64

inch insulation.

IMPORTANT

The expansion cable can only be connected to the
modules such that the red stripe on the cable is on top as
shown below.

!

WARNING

Use supply wires suitable for 30°C above surrounding
ambient.

Status
Comm

0 1 2 3 4 5 6 7

CompactBlock

I/O

1791R-8V8P

8 INPUTS / 8 OUTPUTS - DC POWER

Allen-Bradley

0 1 2 3 4 5 6 7

Remote I/O

Red strip must be on top of ribbon cable.

30360