Rockwell Automation 1791R-XXXX CompactBlock Distributed I/O on Remote I/O Series D I.I. User Manual

Page 34

Advertising
background image

34 CompactBlock Distributed I/O on Remote I/O Series D

Publication

1791R-IN002B-EN-P - August 2003

General Specifications

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal

Shock):

–40 to 85°C (–40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp

Heat):

5-95% non-condensing

Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):

Operating 30g

Non-operating 50g

Vibration

IEC60068-2-6 (Test Fc, Operating):

5g @ 10-500Hz

Conductors Wire Size

Category

14 gauge (2mm

2

) stranded maximum

3/64 inch insulation maximum
2

1, 2

ESD Immunity

IEC 61000-4-2:

6kV contact discharge

8kV air discharge

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1kHz sine-wave 80%AM from 80MHz to 1000MHz

10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

EFT/B Immunity

IEC 61000-4-4:

±2kV at 5kHz on signal ports

±2kV at 5kHz on communications ports

Surge Transient Immunity

IEC 61000-4-5:

±1kV line-line(DM) and ±2kV line-earth(CM) on signal ports

±2kV line-earth(CM) on shielded

ports

Conducted RF Immunity

IEC 61000-4-6:

10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Emissions

CSPR 11:

Group 1, Class A

Advertising