Rockwell Automation 1769-OF2 Compact I/O Analog Modules User Manual

Page 125

Advertising
background image

Publication 1769-UM002B-EN-P - July 2005

Module Diagnostics and Troubleshooting 5-7

1769-OF2 Specific
Configuration
Error

X400

010

0 0000 0000

General configuration error; no additional information

X401

010

0 0000 0001

invalid output range selected (channel 0)

X402

010

0 0000 0010

invalid output range selected (channel 1)

X403

010

0 0000 0011

invalid output data format selected (channel 0)

X404

010

0 0000 0100

invalid output data format selected (channel 1)

X405

010

0 0000 0101

invalid fault value entered for data format selected (channel 0)

X406

010

0 0000 0110

invalid fault value entered for data format selected (channel 1)

X407

010

0 0000 0111

invalid program value entered for data format selected (channel 0)

X408

010

0 0000 1000

invalid program value entered for data format selected (channel 1)

(1)

X represents the “Don’t Care” digit.

Table 5.4 1769-IF4 and -OF2 Extended Error Codes

Error Type

Hex

Equivalent

(1)

Module

Error

Code

Extended Error

Information

Code

Error Description

Binary

Binary

Table 5.5 1769-IF8 Extended Error Codes

Error Type

Hex

Equivalent

(1)

Module

Error

Code

Extended Error

Information

Code

Error Description

Binary

Binary

No Error

X000

000

0 0000 0000

No Error

General Common
Hardware Error

X200

001

0 0000 0000

General hardware error; no additional information

X201

001

0 0000 0001

Power-up reset state

Hardware-
Specific Error

X300

001

0 1000 0000

General hardware error, loss of external 24V dc power

X301

001

0 1000 0001

Microprocessor hardware error

X302

001

1 0000 0010

A/D converter communication error

Advertising