Installation and Wiring 2-21

Figure 2.14 1769-IF4 Wiring Mixed Transmitter Types

(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA minimum

for a single input module.

(2) Series B and later modules provide this option.

+

V in 0 +

V/I in 0 -
I in 0 +
ANLG Com
V in 1 +
V/I in 1 -
I in 1 +
ANLG Com

V in 2 +
V/I in 2 -
I in 2 +
ANLG Com
V in 3 +
V/I in 3 -
I in 3 +
ANLG Com

+24V dc

dc NEUT

+

+

+

+

+

+

+

Single-ended

Voltage

Transmitter

Differential

Voltage

Transmitter

Differential

Current

Transmitter

2-Wire Current

Transmitter

Signal

Signal

Signal

Signal

Supply

Supply

Sensor/Transmi

tter Supply

1769-IF4 Terminal Block

External 24V dc

Power Supply

(optional)

(1)