Rockwell Automation 1769-OF2 Compact I/O Analog Modules User Manual

Page 136

Advertising
background image

Publication 1769-UM002B-EN-P - July 2005

A-6 Specifications

Specification

1769-IF8

Accuracy Drift with
Temperature

Voltage Terminal: ±0.003% per °C
Current Terminal: ±0.0045% per °C

Calibration

The module performs autocalibration on channel enable and
on a configuration change between channels.

Non-linearity (in percent
full scale)

±0.03%

Repeatability

(1)

±0.03%

Module Error over Full
Temperature Range
(0 to +60°C [+32°F to
+140°F])

Voltage: ±0.3%

Current: ±0.5%

Input Channel Configuration via configuration software screen or the user program (by

writing a unique bit pattern into the module’s configuration
file). Refer to your controller’s user manual to determine if
user program configuration is supported.

Module OK LED

On: module has power, has passed internal diagnostics, and
is communicating over the bus.

Off: Any of the above is not true.

Channel Diagnostics

Over- or under-range by bit reporting, process alarms

Maximum Overload at Input
Terminals

(2)

Voltage Terminal: ±30V dc continuous, 0.1 mA
Current Terminal: ±32 mA continuous, ±7.6 V dc

System Power Supply
Distance Rating

8 (The module may not be more than 8 modules away from
the system power supply.)

Recommended Cable

Belden™ 8761 (shielded)

Input Group to Bus Isolation 500V ac or 710V dc for 1 minute (qualification test)

30V ac/30V dc working voltage (IEC Class 2 reinforced
insulation)

Vendor I.D. Code

1

Product Type Code

10

Product Code

38

(1)

Repeatability is the ability of the input module to register the same reading in successive measurements for the same input
signal.

(2)

Damage may occur to the input circuit if this value is exceeded.