Rockwell Automation 1769-OF2 Compact I/O Analog Modules User Manual

Page 138

Advertising
background image

Publication 1769-UM002B-EN-P - July 2005

A-8 Specifications

Output Error Over Full
Temperature Range
(0 to 60°C [32 to +140°F])

Voltage: ±0.8%

Current: ±0.55%

Output Offset Error
(0 to 60°C [32 to +140°F])

±0.05%

Output Impedance

15

Ω (typical)

Open and Short-Circuit
Protection

Yes

Maximum Short-Circuit Current

21 mA

Output Overvoltage Protection

Yes

Time to Detect Open Wire
Condition (Current Mode)

10 ms typical
13.5 ms maximum

Output Response at Power Up
and Power Down

±0.5 V spike for <5 ms

Rated Working Voltage

(6)

30V ac/30V dc

Module OK LED

On: module has power, has passed internal
diagnostics, and is communicating over the bus.

Off: Any of the above is not true.

Channel Diagnostics

Over or under range by bit reporting

output wire broken or load resistance high by bit
reporting (current mode only)

Output Group to Backplane
Isolation

500V ac or 710V dc for 1 minute (qualification test)

30V ac/30V dc working voltage (IEC Class 2 reinforced
insulation)

Vendor I.D. Code

1

Product Type Code

10

Product Code

32

(1)

The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The
module will continue to convert the analog input up to the maximum full scale range. The flag automatically
resets when within the normal operating range.

(2)

Step response is the period of time between when the D/A converter was instructed to go from minimum to full
range until the device is at 63% of full range. Time applies to one or both channels.

(3)

Includes offset, gain, non-linearity and repeatability error terms.

(4)

Output ripple is the amount a fixed output varies with time, assuming a constant load and temperature.

(5)

Repeatability is the ability of the output module to reproduce output readings when the same controller value is
applied to it consecutively, under the same conditions and in the same direction.

(6)

Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the
input signal and the value that floats above ground potential (for example, 10V dc input signal and 20V dc
potential above ground).

(7)

If the optional 24V dc Class 2 power supply is used, the 24V dc current draw from the bus is 0 mA.

Specification

1769-OF2 (Series B and later)

Advertising