Module Data, Status, and Channel Configuration for the Input Modules 3-15

Table 3.10 500 Hz Effective Resolution

1769-IF4
Input
Range

Raw/Proportional Data
Over the Full Input Range

Engineering Units Over
the Full Input Range

Scaled-For-PID Over the
Full Input Range

Percent
Over the Full Input
Range

Bits and
Engineering
Units
Resolution

Decimal
Range and
Count
Value

Resolution

Decimal
Range and
Count
Value

Resolution

Decimal
Range and
Count
Value

Resolution

Decimal
Range and
Count
Value

-10 to
+10V dc

Sign +9
20.51 mV/
64 counts

±32767
Count by 64

21.00 mV/
21 counts

±10500
Count by 21

20.75 mV/
17 counts

-410 to
+16793
Count by 17

Not
Applicable

Not
Applicable

0 to
+5V dc

Sign +8
20.51 mV/
128 counts

-3121 to
+32767
Count by 128

21.00 mV/
21 counts

-500 to
+5250
Count by 21

20.75 mV/
68 counts

-1638 to
+17202
Count by 68

21.00 mV/
42 counts

-1000 to
+10500
Count by 42

0 to
+10V dc

Sign +9
20.51 mV/
64 counts

-1560 to
+32767
Count by 64

21.00 mV/
21 counts

-500 to
+10500
Count by 21

20.75 mV/
34 counts

-819 to
+17202
Count by 34

21.00 mV/
21 counts

-500 to
+10500
Count by 21

+4 to
+20 mA

Sign +9
41.02 µA/
64 counts

+4993 to
+32767
Count by 64

42.00 µA/
42 counts

+3200 to
+2100
Count by 42

41.02 µA/
42 counts

-819 to
+17407
Count by 42

41.60 µA/
26 counts

-500 to
+10625
Count by 26

+1 to
+5V dc

Sign +8
20.51 mV/
128 counts

+3121 to
+32767
Count by 128

21.00 mV/
21 counts

+500 to
+5250
Count by 21

20.75 mV/
84 counts

-2048 to
+17407
Count by 84

20.8 mV/
52 counts

-1250 to
+10625
Count by 52

0 to
+20 mA

Sign +9
41.02 µA/
64 counts

0 to +32767
Count by 64

42.00 µA/
42 counts

0 to +21000
Count by 42

41.51 µA/

34 counts

0 to +17202
Count by 34

42.00 µA/
21 counts

0 to +10500
Count by 21