Analog input modules wiring -19, Analog input modules wiring – Rockwell Automation 1769-OF2 Compact I/O Analog Modules User Manual

Page 43

Advertising
background image

Publication 1769-UM002B-EN-P - July 2005

Installation and Wiring 2-19

Analog Input Modules Wiring

Figure 2.11 1769-IF4 Terminal Layout

Figure 2.12 1769-IF4 Wiring Diagram Showing Differential Inputs

(1) The external power supply must be rated Class 2, with a 24V dc range of 20.4 to 26.4V dc and 60 mA minimum

for a single input module.

(2 ) Series B and later modules provide this option.

V in 0 +

V/I in 0 -

I in 0 +

ANLG Com

V in 1 +

V/I in 1 -

I in 1 +

ANLG Com

V in 2 +

V/I in 2 -

I in 2 +

ANLG Com

V in 3 +

V/I in 3 -

I in 3 +

ANLG Com

dc NEUT

+24V dc

1769-IF4

I in 0+

V in 3 +

+24V dc

V in 1 +

I in 1+

V in 2 +

I in 2+

I in 3+

V in 0 +

ANLG

Com

V/I in 3 -

dc NEUT

V/I in 1 -

ANLG

Com

V/I in 2 -

ANLG

Com

ANLG

Com

V/I in 0 -

Ensure Adjacent Bus Lever is
Unlatched/Latched Before/After
Removing/Inserting Module

D A N G E R

Do Not Remove RTB Under Power
Unless Area is Non-Hazardous.

+

V in 0 +

V/I in 0 -

I in 0+

ANLG Com

V in 1 +

V/I in 1 -

I in 1+

ANLG Com

V in 2 +

V/I in 2 -

I in 2+

ANLG Com

V in 3 +

V/I in 3 -

I in 3+

ANLG Com

dc NEUT

+24V dc

+

-

earth ground

shield locally at

the module

Analog
Source

Belden 8761 cable (or equivalent)

1769-IF4

External 24V dc

Power Supply

(1)

(optional)

(2)

Advertising