4-10 Module Data, Status, and Channel Configuration for the Output Modules

If this selection is enabled [the bit is set (1)] and the system enters the program
mode, it commands the module to convert the user-specified value from the
channel’s program/idle value word (3 or 5) to the appropriate analog output
for the range selected.

1769-OF2 Program/Idle to Fault Enable (PFE0 and PFE1)

If a system currently in program/idle mode faults, this setting (word 0, bit 0;
word 1, bit 0) determines whether the program/idle or fault mode value is
applied to the output. If the selection is enabled [the bit is set (1)], the module
applies the fault mode data value. If the selection is disabled [the bit is reset
(0)], the module applies the program/idle mode data value. The default setting
is disabled.

EXAMPLE

• If the default value, 0000, is used and the range selected

is 0 to 20 mA, the module will output 0 mA for all data
formats.

• If the raw/proportional or engineering units format is

selected and zero is entered as the program/idle value
in either a 1 to 5V dc or 4 to 20 mA range, a
configuration error results.

See Table 4.5 1769-OF2 Valid Output Data Table on

page 4-12 for more examples.

TIP

Not all controllers support this function. Refer to your
controller’s user manual for details.

TIP

Not all controllers support this function. Refer to your
controller’s user manual for details.