USB-to-Data Highway Plus Cable 11

Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

Configure the DH+ Node Address

The cable DH+ node address (station number) is automatically set the first time
the cable sees traffic from RSLinx software to the DH+ network.

To change the node address of the cable, you must do these steps.

1. In RSLinx Classic software, from the Communication menu, choose

Configure Drivers.

2. Choose the driver and click Stop.
3. Click Configure.
4. Enter the new node address and click OK.
5. Cycle power to the cable by disconnecting the 1784-U2DHP cable USB

connector from the USB port, then reconnecting it.

6. Verify the driver is still selected and click Start.
7. Initiate traffic from RSLinx Classic software to the DH+ network.

a. From the Communication menu, choose RSWho.

b. Choose the driver from the list.

Consider the Traffic Analyzer Software

The 1784-U2DHP cable is designed to work with Frontline’s NetDecoder
traffic analyzer software. For more information on Frontline’s product, go to

http://www.rockwellautomation.com/encompass

or

http://www.fte.com

.