USB-to-Data Highway Plus Cable 5

Rockwell Automation Publication 1784-IN045C-EN-P - May 2010

The cable operates at DH+ communication rates of 57.6 Kbps, 115.2 Kbps, and
230.4 Kbps.

The 1784-U2DHP cable supports these DH+ network cable lengths.

Install the Cable

Follow the procedures on the following pages to install the cable.

Obtain the Device Driver for the Cable

Follow these steps to download the device driver for the cable.

1. Visit

http://www.rockwellautomation.com/support/pccards

.

2. Click the 1784_u2dhp.inf file.
3. Save the file to a directory on the computer on which you want to install

the cable.

IMPORTANT

The DH+ communication rate is read only when power is applied.
To change the communication rate, you must disconnect the cable
from the USB port, use the Communication Rate switch to change
the communication rate setting, then reconnect the cable to the
USB port.

DH+ Communication Rate

Max. DH+ Network Cable Length

57.6 Kbps

3048 m (10,000 ft)

115.2 Kbps

1524 m (5000 ft)

230.4 Kbps

762 m (2500 ft)

IMPORTANT

If RSLinx Classic software, version 2.53 or later, is installed on the
computer, the device driver is already installed on the computer.
Skip this section.