Connect the module to the devicenet network – Rockwell Automation 1747-SDN 1747-SDN DeviceNet Scanner Installation Instructions User Manual
Page 10
Advertising
![background image](/manuals/579709/10/background.png)
10 1747-SDN DeviceNet Scanner Module
Publication 1747-IN058F-EN-P - December 2010
3.
Insert the module into the slot you have selected.
4.
Apply firm, even pressure to seat the module in the I/O chassis backplane
connectors.
Connect the Module to the DeviceNet Network
Follow these steps to connect the module to the DeviceNet network.
1.
Turn off the network power supply.
ATTENTION
To comply with the CE Low Voltage Directive (LVD), DeviceNet must be
powered from a source compliant with the following:
• Safety Extra Low Voltage (SELV)
• Protected Extra Low Voltage (PELV).
To comply with UL restrictions, DeviceNet must be powered from a source
compliant with the following:
• Class 2
• Limited Voltage/Current.
Advertising