16 1747-SDN DeviceNet Scanner Module

Publication 1747-IN058F-EN-P - December 2010

Specifications

98

Unrecoverable firmware failure.

Service or replace your module.

99

Unrecoverable hardware failure.

Service or replace your module.

E2

RAM Test Failure

Service or replace your module.

E4

Lost power during FLASH upgrade

Service or replace your module.

E5

No application code

Service or replace your module.

E9

Module memory has been flushed for factory
default settings.

Cycle module power to recover.

SLC DeviceNet Scanner — 1747-SDN

Attribute

Value

Module location

SLC 5/02 or later chassis

Module defaults

Node Address – 63
Baud Rate – 125 Kbps

Power consumption
- Backplane current
- DeviceNet

5V DC, 500 mA
24V DC, 90 mA Class 2

Isolation voltage

30V (continuous), Basic Insulation Type
Tested at 500V AC for 60 s, DeviceNet to backplane

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0…60

o

C (32…140

o

F)

Temperature, non-operating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bc, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

-40…85

o

C (-40…185

o

F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):
2 g @10…500 Hz

Shock

IEC60068-2-27:1987, Test Ea (Unpackaged shock, ES#002)
Operating — 30 g
Non-operating — 50 g

Numeric
Code

Description

Corrective Action