Rockwell Automation 1747-SDN 1747-SDN DeviceNet Scanner Installation Instructions User Manual
Page 15
 
1747-SDN DeviceNet Scanner Module 15
Publication 1747-IN058F-EN-P - December 2010
82
Error detected in sequence of fragmented I/O 
messages from device.
Check scan list table entry for slave device to 
make sure that input and output data lengths 
are correct. Check slave device configuration.
83
Slave device is returning error responses when 
module attempts to communicate with it.
Check accuracy of scan list table entry. Check 
slave device configuration. Slave device may 
be in another master’s scan list. Reboot slave 
device.
84
Module is initializing the DeviceNet network.
None. This code clears itself once module 
attempts to initialize all slave devices on the 
network.
85
Data size was incorrect for this device at 
runtime.
Slave device is transmitting incorrect length 
data.
Verify device is not configured for variable poll 
connection size.
Try replacing the device.
86
Device is producing zero length data (idle 
state) while module is in Run mode.
Check device configuration and slave node 
status.
87
The primary owner has not allocated the slave.
Put the primary owner online.
88
The connection choices (polled, strobed) 
between the primary connection and the 
shared input only connection do not match.
Reconfigure the shared input-only connection 
choices to be the same as, or a subset of, the 
choices for the primary connection.
89
Slave device initialization using Auto Device 
Replacement parameters failed.
Put the slave device into configurable mode.
If the slave is configured offline, check its EDS 
file.
Check to see if the slave device has been 
replaced with an incompatible device.
90
User has disabled communication port.
Check Module Command Register for DISABLE 
bit set.
91
Bus-off condition detected on comm port. 
Module is detecting communication errors.
Check DeviceNet connections and physical 
media integrity. Check system for failed slave 
devices or other possible sources of network 
interference.
92
No network power detected on communication 
port.
Provide network power. Make sure that 
module drop cable is providing network power 
to module comm port.
95
Application FLASH update in progress.
None. Do not disconnect the module while 
application FLASH is in progress. You will lose 
existing data in the module memory.
97
Module operation halted by user command.
Check Module Command Register for HALT bit 
set.
Numeric 
Code
Description
Corrective Action