12 1747-SDN DeviceNet Scanner Module

Publication 1747-IN058F-EN-P - December 2010

Apply Chassis Power

When you apply chassis power, the module numeric indicators cycle through the following
displays.

• Seven-segment lamp test (88)
• Firmware major revision (01…7F hexadecimal)
• Firmware minor revision (01…FF hexadecimal)
• Communication rate (indicates 00 for the default of 125, 01 for 250, or 02 for

500 Kbps)

• Node address (00…63 with 63 as the default)

Use the RSNetWorx for DeviceNet software to change the communication rate and node
address.

Refer to the Numeric Code Display Summary table on page 14 for a complete listing of
numeric displays.

Interpret the LED Indicators

The bicolor (green/red) module status indicator (MODULE) on the front of your module
displays module status. It indicates whether the module has power and is functioning
properly.

Module Status LED Indicator

Indicator Color

Description

Corrective Action

Off

There is no power applied to the
module.

Verify power connections and apply
power.

Green

The module is operating normally.

No action required.

Flashing Green

The module is not configured.

Configure the module.

Flashing Red

There is an invalid configuration.

Check configuration setup.

Red

The module has an unrecoverable
fault.

Replace the module.

DeviceNet

STATUS

MODULE NET

ADDRESS/ERROR

Module
Numeric
Indicators