6 1747-SDN DeviceNet Scanner Module

Publication 1747-IN058F-EN-P - December 2010

Pass-through

The SLC 500 pass-through feature allows communication with the DeviceNet network from
another network. This feature can be used to adjust and fine tune the nodes on your network.

The pass-through feature is not intended to replace a 1770-KFD, 1784-PCD, 1784-PCID, or
1784-PCIDS connection to the network.

To use the pass-through feature you must meet the following hardware, software and
firmware requirements.

U2DN module

The pass-through feature is not intended to replace a 1784-U2DN, 1770-KFD, 1784-PCD,
1784-PCID, or 1784-PCIDS connection to the network.

Pass-through Requirements

SLC 500 Processor

1747-SDN Firmware

RSLinx Software

M0 and M1 Files

SLC 5/03 or later

4.015…5.001

2.10 or later

Configured for 361 words

SLC 5/03 or later

6.001 or later

2.31 or later

Configured for 395 words