Removing the linking device, Connecting power – Rockwell Automation 1788-CN2FF ControlNet-to-FOUNDATION Fieldbus H1 Linking Device User Manual User Manual

Page 12

Advertising
background image

1788-6.5.1 - January 1999

2-2

Hardware Installation and Configuration

3. Slide the linking device to the desired position on the DIN rail. After it is

in position, push the rail snap into the locked position to lock it in place
on the DIN rail.

Removing the Linking Device

To remove a linking device, unlock it from the DIN rail by placing a
screwdriver in the slot on the rail snap and opening the rail snap to the
unlocked position as shown in step 1 on page 2-1. Then lift the device off of
the rail.

Connecting Power

An 11-30V dc power supply is required by each linking device. The linking
device filters and regulates this supplied power. The power connector is a
6-pin screw terminal connector. The pinout for the power connector is
shown in Figure 2.1.

Figure 2.1 Power Connector Pinout

Rail Clip Locked

Rail Clip Unlocked

(Position Device Along DIN Rail)

DIN Rail

Linking

Device

v

v

v

c c

c

11-30 VDC

Backup Power

Supply

(optional)

+

+

11-30 VDC

Primary Power

Supply

V

C

To adjacent device

(optional connection)