Controlnet network status leds, Fieldbus network status leds – Rockwell Automation 1788-CN2FF ControlNet-to-FOUNDATION Fieldbus H1 Linking Device User Manual User Manual

Page 17

Advertising
background image

1788-6.5.1 - January 1999

Hardware Installation and Configuration

2-7

ControlNet Network Status LEDs

The ControlNet network status LEDs are located on the front of the linking
device, beside the ControlNet BNC connectors, as shown in Figure 1.2.
They indicate the state of the ControlNet connected to the BNC connectors.
These LEDs do not reflect anything about the status of the network if the
linking device is connected to the network through the network access port
(NAP). If more than one state is present, the LEDs always reflect the
highest priority status present on the network. Table 2.B describes the LED
states and the priority of each status.

Fieldbus Network Status LEDs

Each Fieldbus port on the linking device has an LED to indicate the
functional states of the port. Table 2.C describes each state.

Table 2.B Description of ControlNet Network Status LED States

LED State

Priority

How to View

Cause

Both steady off

1

(highest)

View together

Reset or no power

Both steady red

2

Failed to link interface to ControlNet

Alternating red & green

3

Self testing

Alternating red

4

Bad node configuration (such as
duplicate ControlNet network address)

Steady off

5

View

independently

Channel disabled or not supported

Flashing red & green

6

Invalid link configuration

Flashing red

7

Link fault or no frames received

Flashing green

8

Temporary channel error or listen only

Steady green

9

(lowest)

Normal operation

Table 2.C Description of Fieldbus Network Status LED States

LED State

Meaning

Off

Fieldbus port not receiving packets

Steady green

Fieldbus port is alive as Link Active Scheduler

Flashing red and green

Fieldbus port is seeing traffic, but is at a default or
visitor address

Flashing red

Fieldbus port encountered transient, non-fatal network
error

Steady red

Fieldbus port encountered fatal network error