Using the ControlNet-to-FOUNDATION Fieldbus H1 Linking Device

ControlNet Analog Input Objects

The linking device creates an instance of a ControlNet AI object for every
wired channel in the MAI block instances. Each instance of the ControlNet
AI object has the attributes and access rules shown in Table 4.A.

All attributes in Table 4.A are created if a standard Fieldbus AI function
block is connected to a channel of an MAI block. Otherwise, only Value,
CNStatus, TagDesc, and FFstatus are created.

Alarm Handling for Analog Inputs

You can configure Fieldbus AI function blocks to detect and report alarms.

Four process alarms (HI_HI_ALM, HI_ALM, LO_LO_ALM, and
LO_ALM) are exposed through the ControlNet AI object. When you
connect an AI function block to an MAI block, the NI-FBUS Configurator
configures the field device to send the four alarms to the linking device.

In Fieldbus terminology, confirming an alarm means that the alarm has been
received by an operator, and acknowledging an alarm means that the
operator has taken the necessary action.

When an alarm condition is detected by a Fieldbus function block, the alarm
is said to be ACTIVE. An active alarm should be Acknowledged and
Confirmed after the condition causing the alarm is corrected. When the
function block detects the alarm condition is no longer present, the alarm is
said to be CLEARED. The CLEARED state must be Confirmed when it is
detected. Users of the LD use the alarm attributes to process Fieldbus
alarms.

Each attribute corresponding to a process alarm has the three alarm-related
bits as shown in Figure 4.3.

Table 4.A ControlNet Analog Input Object Attributes

Attribute

Number

Name

Type

Access

Initial Value

Remarks

3

Value

Float

Get

0

4

CNStatus

Boolean

Get

Bad

ControlNet status. 0-Good; 1-Bad.

107

LoFlag

uint8

Get/Set

0

See Alarm Handling for Analog Inputs

108

HiFlag

uint8

Get/Set

0

See Alarm Handling for Analog Inputs

109

LoLoFlag

uint8

Get/Set

0

See Alarm Handling for Analog Inputs

110

HiHiFlag

uint8

Get/Set

0

See Alarm Handling for Analog Inputs

150

FFstatus

uint8

Get

Bad:Out of
Service

Fieldbus status of the value; obtained from the
Fieldbus device.

151

TagDesc

String

Get

As configured

Tag of the Fieldbus function block that is
represented by this object instance.