Specifications, Appendix – Rockwell Automation 1788-CN2FF ControlNet-to-FOUNDATION Fieldbus H1 Linking Device User Manual User Manual

Page 45

Advertising
background image

1788-6.5.1 - January 1999

Appendix

A

Specifications

Table A.A Linking Device Specifications

Type

Specifications

Environmental

Operating Temperature: 0 to 60° C (32 to 140° F)

Storage Temperature: -40 to 85° C (-40 to 185° F)

Relative Humidity: 5 to 90% (non-condensing)

Vibration

Operating - 2Gs each axis

Tested 2Gs @ 10 - 500 Hz per IEC 68-2-6

Communication

ControlNet - redundant media and network access port

F

OUNDATION

Fieldbus H1, 2 independent channels

LAS on both channels

Time Master on both channels

Power Requirements

11-30V dc; 270 mA @ 24V dc (typical)

Indicators

Module Status

Fieldbus Status, 1 each channel

ControlNet Status, 1 each connection

Connectors

ControlNet - BNC connectors

Network Access Port - RJ45

Fieldbus - 9-pin sub-D connectors

Conductors/Wire Size/Category

Category 2

1

Mounting

35 mm DIN rail

ControlNet Channel Selection

two 10-position rotary switches

Agency Certification
(when product is marked)

• Information Technology Equipment

• Industrial Control Equipment

• Class I, Div. 2, Groups A, B. C, D

Hazardous Location

• EN 50082-1, 2

• EN 55022, Radiated Emission Class B

• EN 61131-2

FCC Part 15, SubPart B

1

Refer to the Industrial Automation Wiring and Grounding Guidelines for Noise Immunity, publication 1770-4.1.