ControlNet Discrete Input Objects

The linking device creates an instance of a ControlNet DI object for every
wired channel in the MDI block instances. Each instance of the ControlNet
DI object has the attributes and access rules shown in Table 4.C.

All attributes in Table 4.C are created if a standard Fieldbus DI function
block is connected to a channel on an MDI block. Otherwise, DiscAlmFlag
is not created.

Alarm Handling for Discrete Inputs

You can configure Fieldbus DI function blocks to detect and report alarms.

The process alarm (DISC_ALM) are exposed through the ControlNet DI
object. When you connect a DI function block to an MDI block, the
NI-FBUS Configurator configures the field device to send the alarm to the
linking device.

In Fieldbus terminology, confirming an alarm means that the alarm has been
received by an operator, and acknowledging an alarm means that the
operator has taken the necessary action.

When an alarm condition is detected by a Fieldbus function block, the alarm
is said to be ACTIVE. An active alarm should be Acknowledged and
Confirmed after the condition causing the alarm is corrected. When the
function block detects the alarm condition is no longer present, the alarm is
said to be CLEARED. The CLEARED state must be Confirmed when it is
detected. Users of the LD use the alarm attributes to process Fieldbus
alarms.

Each attribute corresponding to a process alarm has the three alarm-related
bits as shown in Figure 4.8.

Table 4.C ControlNet Discrete Input Object Attributes

Attribute

Number

Name

Type

Access

Initial Value

Remarks

3

Value

Boolean

Get

0

4

CNStatus

Boolean

Get

Bad

ControlNet status. 0-Good; 1-Bad.

150

Ffstatus

uint8

Get

Bad:Out of Service

Fieldbus status of the value; obtained from
the Fieldbus device.

151

TagDesc

String

Get

As configured

Tag of the Fieldbus function block that is
represented by this object instance.

156

DiscAlmFlag

uint8

Get/Set

0

See Alarm Handling for Discrete Inputs