Chapter 3 Module Data, Status, and Channel Configuration

Channel Configuration

Each channel is independently configured via a group of six
consecutive words in the Configuration Data file. The first two words
of the group consist of bit fields, the settings of which determine how
the channel operates. See the tables below and the descriptions that
follow for valid configuration settings and their meanings. The default
bit status of the configuration file is all zeros.

Bit Definitions for Channel Configuration Words

Define

To Choose

Make these bit settings

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Input Filter Selection

60 Hz

0

0

0

0

50 Hz

0

0

0

1

16 Hz

0

0

1

0

315 Hz

0

0

1

1

1365 Hz

0

1

0

0

Enable Interrupt

(1)

(2)

(EI)

Enable

1

Disable

0

Process Alarm Latch

(2)

(AL)

Enable

1

Disable

0

Enable Process Alarms
(EA)

Enable

1

Disable

0

Enable Channel (EC)

Enable

1

Disable

0

(1) Alarm interrupts are not supported by all bus masters. Check your controller’s user manual to determine if expansion I/O interrupts are supported.
(2) Do not set this bit to 1 unless the Enable Process Alarms (EA) bit is also set to 1 for the same channel.

1769-IF16C Module: Bit Definitions for Input Range and Input Data Configuration Words

Define

To Choose

Make these bit settings

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Input Range
Select

4…20 mA

0

0

0

0

0…20 mA

0

0

0

1

Input Data
Format Select

Proportional Counts

0

0

0

Engineering Units

0

0

1

Scaled for PID

0

1

0

Percent Range

0

1

1