Enable/disable channel (ec) input filter selection, Enable/disable channel (ec), Input filter selection – Rockwell Automation 1769-IF16V Compact High Density Analog Input Modules User Manual

Page 39

Advertising
background image

Publication 1769-UM018A-EN-P - October 2008

39

Module Data, Status, and Channel Configuration Chapter 3

Enable/Disable Channel (EC)

This configuration selection lets each channel be enabled individually.

Input Filter Selection

The input filter selection field lets you select the filter frequency for
each channel. The filter frequency affects the noise rejection
characteristics, channel step response, and module update time, as
explained below.

Noise Rejection

The modules use a digital filter that provides noise rejection for the
input signals. The filter is programmable, allowing you to select from
five filter frequencies for each channel. A lower frequency (60 Hz
versus 315 Hz) can provide better noise rejection but it increases
channel update time.

Normal Mode Rejection is better than 50 dB at 50 and 60 Hz, with the
50 and 60 Hz filters selected, respectively. Transducer power supply
noise, transducer circuit noise, or process variable irregularities may
also be sources of normal mode noise.

1769-IF16V Module: Bit Definitions for Input Range and Input Data Configuration Words

Define

To Choose

Make these bit settings

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Input
Range
Select

-10…+10V

0

0

0

0

0…5V

0

0

0

1

0…10V

0

0

1

0

1…5V

0

0

1

1

Input
Data
Format
Select

Proportional Counts

0

0

0

Engineering Units

0

0

1

Scaled for PID

0

1

0

Percent Range

0

1

1

TIP

When a channel is not enabled (0), no voltage or
current reading is provided to the controller by the
A/D converter.

Advertising