Publication 1769-UM018A-EN-P - October 2008

Appendix A Specifications

Input Specifications

Attribute

1769-IF16C

1769-IF16V

Analog normal operating ranges

(1)

0…20 mA, 4…20 mA

±10V DC, 0 …10V DC, 0…5V DC, 1…5V DC

Full scale analog ranges

(1)

0…21 mA, 3.2…21 mA

±10.5V DC, -0.5…10.5V DC, -0.5…5.25V DC,
0.5…5.25V DC

Number of inputs

16 single-ended

Converter type

Sigma Delta

Response speed per channel

Input filter and configuration dependent.

Resolution, max

(2)

16 bits (unipolar)
15 bits plus sign (bipolar)

Rated working voltage

(3)

30V AC/30V DC

Common mode voltage range

(4)

±10V DC maximum per channel

Common mode rejection

greater than 60 dB at 50 and 60 Hz with the 16 Hz filter selected, respectively.

Input impedance

249

Ω

Greater than 1 M

Ω

(typical)

Overall accuracy

(5)

0.5% full scale at 25 °C (77 °F) for 16 Hz, 50
Hz, and 60 Hz filters

0.35% full scale at 25 °C (77°F) for 16 Hz, 50
Hz, and 60 Hz filters

Accuracy drift with temperature

±0.0045% per °C

±0.003% per °C

Calibration

None required

None required

Non-linearity (in percent full scale)

±0.03%

±0.03%

Repeatability

(6)

±0.03% for 16 Hz filter

±0.06% for 16 Hz filter

Module error over full temperature range
(0…60 °C [32 °F…140 °F])

1.25% for 16 Hz filter

1.0% for 16 Hz, 50 Hz, and 60 Hz filters

Channel diagnostics

Over- or under-range by bit reporting, process alarms

Maximum overload at input terminals

(7)

±28 mA continuous, 7.0 V DC

±30V DC continuous, 0.03 mA

Input group to bus isolation

500V AC or 710V DC for 1 minute (qualification test)
30V AC/30V DC working voltage (IEC Class 2 reinforced insulation)

(1) The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will continue to convert the analog input up to the

maximum full scale range. The flag automatically resets when within the normal operating range.

(2) Resolution is dependent upon your filter selection.
(3) Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input signal and the value that floats above ground

potential (for example, 10V DC input signal and 20V DC potential above ground).

(4) For proper operation, the plus input terminals must be within ±10V DC of analog common.
(5) Includes offset, gain, non-linearity and repeatability error terms.
(6) Repeatability is the ability of the input module to register the same reading in successive measurements for the same input signal.
(7) Damage may occur to the input circuit if this value is exceeded.