Chapter 4 Module Diagnostics and Troubleshooting

Invalid Input Format Selected

These error codes occur when the 3-bit input format code for the
indicated channel is not one of the assigned input format codes for
the module.

See

1769-IF16C Module: Bit Definitions for Input Range and Input

Data Configuration Words on page 38

or

1769-IF16V Module: Bit

Definitions for Input Range and Input Data Configuration Words on
page 39

for details on the assigned input format codes for each

module.

Alarm Not Enabled

These error codes occur when a channel is enabled and the Alarm
Latch and/or the Enable Interrupt control bits for that channel are set
but the Enable Alarm bit is not set.

See

Bit Definitions for Channel Configuration Words on page 38

for

details on setting the process alarm control bits for the modules.

Invalid Alarm Data

These error codes occur when the data entered for the high or low
process alarms for a channel exceed the full-range limits of the
channel. The full-range limits for a channel are a function of the input
range and the input format selected for the channel.

See

Valid Input Data Word Formats/Ranges on page 42

for details on

the full-range limits for each data range and data format.

These error codes may also occur if the deadband value entered for a
channel is less than 0, or is greater than or equal to one-half times the
channel’s high alarm value minus the channel’s low alarm value.