Module Diagnostics and Troubleshooting Chapter 4

Channel Diagnostics

When an input channel is enabled, the modules perform a diagnostic
check to see that the channel has been properly configured. In
addition, the modules check each channel during every conversion
cycle for over-range and under-range, high and low process alarm
conditions, and open-circuit conditions.

Out-of-range Detection

Whenever data received at an input is out of the defined normal
operating range, an over-range or under-range error is indicated in the
Input Data file.

Process Alarm Detection

Whenever data received at an input meets or exceeds that channel’s
configured process alarm limits, a high alarm or low alarm error is
indicated at the Input Data file.

Open-circuit Detection

The 1769-IF16V module provides open-circuit detection on all
enabled channels. Whenever an open-circuit condition occurs, the
over-range error bit for that channel is set and the channel’s input data
reading will be at the maximum, full-range value in the Input Data
file.

The 1769-IF16C module also provides open-circuit detection on all
enabled channels. Whenever an open-circuit condition occurs, the
under-range error bit for that channel is set and the channel’s input
data reading will be at the minimum, full-range value in the Input
Data file.

Possible causes of an open circuit include:

the sensing device may be broken.

a wire may be loose or cut.

the sensing device may not be installed on the configured
channel.