Non-critical vs. critical module errors, Module error definition table, Module error field – Rockwell Automation 1769-IF16V Compact High Density Analog Input Modules User Manual

Page 50

Advertising
background image

50

Publication 1769-UM018A-EN-P - October 2008

Chapter 4 Module Diagnostics and Troubleshooting

Non-critical vs. Critical
Module Errors

Non-critical module errors are typically recoverable. Channel errors
(over-range or under-range errors, process alarms, and open circuit
errors) are non-critical. Non-critical errors are indicated in the module
input data table.

Critical module errors are conditions that prevent normal or
recoverable operation of the system. When these types of errors
occur, the system typically leaves the run or program mode of
operation until the error can be dealt with.

Critical module errors are indicated in

Error Codes on page 51

.

Module Error Definition
Table

Module errors are expressed in two fields as four-digit Hex format
with the most significant digit as don’t care and irrelevant. The two
fields are Module Error and Extended Error Information.

Module Error Field

The purpose of the module error field is to classify module errors into
three distinct groups, as described in the table below. The type of
error determines what kind of information exists in the extended error
information field. Refer to your controller manual for details.

Module Error Table

Don’t Care Bits

Module Error

Extended Error Information

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Hex Digit 4

Hex Digit 3

Hex Digit 2

Hex Digit 1

Module Error Types

Error Type

Module Error

Field Value

Bits 11…09

(Bin)

Description

No Errors

000

No error is present. The extended error field holds
no additional information.

Hardware
Errors

001

General and specific hardware error codes are
specified in the extended error information field.

Configuration
Errors

010

Module-specific error codes are indicated in the
extended error field. These error codes correspond
to options that you can change directly. For
example, the input range or input filter selection.

Advertising