Error codes, Extended error information field – Rockwell Automation 1769-IF16V Compact High Density Analog Input Modules User Manual

Page 51

Advertising
background image

Publication 1769-UM018A-EN-P - October 2008

51

Module Diagnostics and Troubleshooting Chapter 4

Extended Error Information Field

Depending upon the value in the module error field, the extended
error information field can contain error codes that are
module-specific or common to all 1769 analog modules.

Error Codes

Error codes can help troubleshoot your module.

During system configuration, if you set the fields in the configuration
file to invalid or unsupported values, the modules generate a
configuration error and the system controller enters a Fault condition.
The invalid configuration data must be corrected and the program
downloaded again for the system to enter Run mode. You cannot
change module configuration data while the system is in Run mode.
Any changes are ignored by the modules, which continue to operate
with their previous configuration.

TIP

If no errors are present in the module error field, the
extended error information field will be set to zero.

Extended Error Codes for Hardware Errors

Error Type

Hex

Equivalent

(1)

Module

Error

Code

Extended Error

Information

Code

Error Description

Binary

Binary

No Error

X000

000

0 0000 0000

No Error

General Common
Hardware Error

X200

001

1 0000 0000

General hardware error; no additional information

X201

001

1 0000 0001

Power-up reset state

Hardware-
Specific Error

X300

001

1 0000 0000

General hardware error

X301

001

1 0000 0001

Microprocessor hardware error

X302

001

1 0000 0010

A/D converter communication error

(1) X represents the Don’t Care digit. Module hardware error codes are typically presented in their Hex Equivalent by the programming software.

Extended Error Codes for Configuration Errors

Hex Equivalent

(1)

Module

Error Code

Extended Error

Information Code

Error Description

Binary

Binary

X400

010

0 0000 0000

General configuration error; no additional information

X401

010

0 0000 0001

Invalid input range selected (channel 0)

X402

010

0 0000 0010

Invalid input range selected (channel 1)

X403

010

0 0000 0011

Invalid input range selected (channel 2)

Advertising