Publication 1785-10.5 - November 1998

2-2

Set up the Hardware

Install the Hardware

Configure the I/O Chassis

Regardless of this switch setting, outputs are turned off when any of the following occurs:

- processor detects a runtime error
- an I/O chassis backplane fault occurs
- you select program or test mode
- you set a status file bit to reset a local rack

`

If an EEPROM module is not installed and processor memory is valid, the processor's PROC LED indicator blinks,

and the processor sets S:11/9, bit 9 in the major fault status word. To clear this fault, change the processor from
program mode to run mode and back to program mode.

´

If the processor's keyswitch is set in REMote, the processor enters remote RUN after it powers up and has its

memory updated by the EEPROM module.

ˆ

A processor fault (solid red PROC LED) occurs if processor memory is not valid.

˜

You cannot clear processor memory when this switch is on.

4

5

2 - slot

1 - slot

1/2 - slot

1

Always
Off

19309

6

7

Outputs of this I/O chassis remain in their last state when
a hardware failure occurs.

Outputs of this I/O chassis are turned off when a
hardware failure occurs.

EEPROM memory transfer to processor memory at power-up.

` ´

EEPROM memory transfers to processor memory if processor memory
not valid.

EEPROM memory does not transfer to processor memory.

ˆ

Processor memory protection disabled.

Processor memory protection enabled.

˜

Not allowed

Processor Memory Protection

Switch

8

off

on

EEPROM Transfer

Addressing

Last State

Switch

on

off

Switches

Switches

off

off

off

on

on

off

on

on

off

off

on

on

on

off

Set the backplane switches.

1

Pressed in
at top ON (closed)

Pressed in
at bottom OFF (open)

12

3

4

5

6

7

8

O

N

O

F

F

1

1

2, 3

4

5

5

4

3

2

1