Troubleshoot the Processor System

Troubleshoot the Processor Communication Channels

FORCE

Amber
(steady)

SFC and/or I/O forces
enabled

Normal operation

No action required

Amber
(blinking)

SFC and/or I/O forces
present but not
enabled

Off

SFC and/or I/O forces
not present

COMM

Off

No transmission on
channel 0

Normal operation if
channel is not being
used

Green
(blinking)

Transmission on
channel 0

Normal operation if
channel is being used

Indicator

Color

Description

Probable Cause

Recommended Action

Indicator

Color

Channel Mode

Description

Probable Cause

Recommended Action

A or B

Green
(steady)

Remote I/O Scanner

Active Remote I/O link, all
adapter modules are present
and not faulted

Normal operation

No action required

Remote I/O Adapter

Communicating with scanner

DH+

Processor is transmitting or
receiving on DH+ link

Green
(blinking
rapidly or
slowly)

Remote I/O Scanner

At least one adapter is
faulted or has failed

• Power off at

remote rack

• Cable broken

• Restore power to the

rack

• Repair cable

DH+

No other nodes on network

Red
(steady)

Remote I/O Scanner
Remote I/O Adapter
DH+

Hardware fault

Hardware error

• Turn power off, then

on.

• Check that the

software
configurations match
the hardware set-up.

• Replace the processor.

Red
(blinking
rapidly or
slowly)

Remote I/O Scanner

Faulted adapters detected

• Cable not

connected or is
broken

• Power off at

remote racks

• Repair cable

• Restore power to racks

DH+

Bad communication on DH+

Duplicate node
detected

Correct station address

Off

Remote I/O Scanner
Remote I/O Adapter
DH+

Channel offline

Channel is not
being used

Place channel online if
needed

A

A

B