Troubleshoot the ethernet status indicators – Rockwell Automation 1785-Lx0E,D178510.5 QUICK START ETHERNET PLC-9 User Manual
Page 21

Publication 1785-10.5 - November 1998
Troubleshoot the Processor System
4-3
Troubleshoot the Ethernet Status Indicators
Indicator
Color
Description
Probable Cause
Recommended Action
STAT
Solid red
Critical hardware fault
Processor requires
internal repair
Contact Allen-Bradley
Global Technical Support
(GTS)
Blinking red
Hardware or software fault
(detected and reported via a
code)
Fault-code dependent
Contact Allen-Bradley GTS
Off
Ethernet interface is functioning
properly but it is not attached to
an active Ethernet network
Normal operation
Attach the processor to an
active Ethernet network
Green
Ethernet channel 2 is
functioning properly and has
detected that it is connected to
an active Ethernet network
Normal operation
No action required
XMIT
green
lights (green) briefly when the
Ethernet port is transmitting a
packet. It does not indicate
whether or not the Ethernet port
is receiving a packet.
ENET
STAT
RUN
ENET
XMIT