Wire Size and Terminal Screw Torque

Each terminal accepts two wires with the following restrictions.

Configure the 1769-OF4 Module

The following I/O memory mapping lets you configure the 1769-OF4 module.

Output Data File

For each module, slot x, words 0…3 in the output data file contain the control
program’s directed state of the module’s analog output channels. Word 4 contains
the cancel output-channel-clamp alarm control bits.

The bits are defined as follows:

SGN = Sign bit in 2’s complement format.

NU = Not used. Bit must be set to 0.

CHOx = Cancel High Clamp Alarm Latch for Output x: Allows each output
high-clamp-alarm latch to be individually cancelled. NOTE: Cancel = 1.

CLOx = Cancel Low Clamp Alarm Latch for Output x: Allows each output
low-clamp-alarm-latch to be individually cancelled. NOTE: Cancel = 1.

Wire Type

Wire Size

Terminal Screw
Torque

Retaining Screw
Torque

Solid

Cu-90 °C (194 °F)

14…22 AWG
(2.08…0.33 mm

2

)

0.68 N•m (6 lb•in)

0.46 N•m (4.1 lb•in)

Stranded

Cu-90 °C (194 °F)

16…22 AWG
(1.31…0.33 mm

2

)

0.68 N•m (6 lb•in)

0.46 N•m (4.1 lb•in)

Word/Bit 15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word 0

SGN

Analog Output Data Channel 0

Word 1

SGN

Analog Output Data Channel 1

Word 2

SGN

Analog Output Data Channel 2

Word 3

SGN

Analog Output Data Channel 3

Word 4

NU

NU NU NU NU NU NU NU CL

O3

CH
O3

CL
O2

CH
O2

CL
O1

CH
O1

CL
O0

CH
O0