Compact I/O Analog Output Module 9

Publication 1769-IN087A-EN-P - August 2009

Mount Module to Panel

Mount the module to a panel by using two screws per module. Use M4 or #8
panhead screws. Mounting screws are required on every module.

Mount Module to Panel by Using the Dimensional Template

Locate holes every 17.5 mm (0.689 in.) to allow for a mix of single-wide and
one-and-a-half-wide modules (for example, the 1769-OA16 module).

Mount Module to Panel by Using Modules as a Template

This procedure lets you use the assembled modules as a template for drilling holes
in the panel. See

Mount Module to Panel by Using the Dimensional Template on

page 9

if you have sophisticated panel mounting equipment.

On a clean work surface, assemble no more than three modules.

Due to module-mounting hole tolerance, it is important to follow this procedure.

1. Using the assembled modules as a template, carefully mark the center of all

module-mounting holes on the panel.

2. Return the assembled modules to the clean work surface, including any

previously mounted modules.

3. Drill and tap the mounting holes for the recommended M4 or #8 screws.

4. Place the modules back on the panel, and check for proper hole alignment.

132 mm (5.197 in.)

122.6 mm (4.826 in.)

Spacing for single-wide modules 35 mm (1.378 in.)

Spacing for one-and-a-half wide modules 52.5 mm (2.067 in.)

Refer to host controller documentation for this dimension.

NOTE: Overall spacing
tolerance ±0.44 mm (0.016 in.)

Host Contro

ller