Rockwell Automation 1769-OF4 Compact I/O Analog Output Module User Manual

Page 16

Advertising
background image

16

Compact I/O Analog Output Module

Publication 1769-IN087A-EN-P - August 2009

Configuration Data File

Word/Bit 15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word 0

EC

NU

EHI ELI

LC

ER FM PM NU PFE

Word 1

NU

Format Ch0

NU

Type/Range Sel Ch0

Word 2

SGN

Fault Value Channel 0

Word 3

SGN

Program (Idle) Value Channel 0

Word 4

SGN

Clamp High Data Value Channel 0

Word 5

SGN

Clamp Low Data Value Channel 0

Word 6

SGN

Ramp Rate Channel 0

Word 7

NU

Word 8

EC

NU

EHI ELI

LC

ER FM PM NU PFE

Word 9

NU

Format Ch1

NU

Type/Range Sel Ch1

Word 10

SGN

Fault Value Channel 1

Word 11

SGN

Program (Idle) Value Channel 1

Word 12 SGN

Clamp High Data Value Channel 1

Word 13 SGN

Clamp Low Data Value Channel 1

Word 14 SGN

Ramp Rate Channel 1

Word 15

NU

Word 16

EC

NU

EHI ELI

LC

ER FM PM NU PFE

Word 17

NU

Format Ch2

NU

Type/Range Sel Ch2

Word 18

SGN

Fault Value Channel 2

Word 19

SGN

Program (Idle) Value Channel 2

Word 20 SGN

Clamp High Data Value Channel 2

Word 21 SGN

Clamp Low Data Value Channel 2

Word 22 SGN

Ramp Rate Channel 2

Word 23

NU

Word 24

EC

NU

EHI ELI

LC

ER FM PM NU PFE

Word 25

NU

Format Ch3

NU

Type/Range Sel Ch3

Word 26

SGN

Fault Value Channel 3

Word 27

SGN

Program (Idle) Value Channel 3

Word 28 SGN

Clamp High Data Value Channel 3

Word 29 SGN

Clamp Low Data Value Channel 3

Word 30 SGN

Ramp Rate Channel 3

Word 31

NU

Advertising