Rockwell Automation 1769-OF4 Compact I/O Analog Output Module User Manual
Page 16

16
Compact I/O Analog Output Module
Publication 1769-IN087A-EN-P - August 2009
Configuration Data File
Word/Bit 15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word 0
EC
NU
EHI ELI
LC
ER FM PM NU PFE
Word 1
NU
Format Ch0
NU
Type/Range Sel Ch0
Word 2
SGN
Fault Value Channel 0
Word 3
SGN
Program (Idle) Value Channel 0
Word 4
SGN
Clamp High Data Value Channel 0
Word 5
SGN
Clamp Low Data Value Channel 0
Word 6
SGN
Ramp Rate Channel 0
Word 7
NU
Word 8
EC
NU
EHI ELI
LC
ER FM PM NU PFE
Word 9
NU
Format Ch1
NU
Type/Range Sel Ch1
Word 10
SGN
Fault Value Channel 1
Word 11
SGN
Program (Idle) Value Channel 1
Word 12 SGN
Clamp High Data Value Channel 1
Word 13 SGN
Clamp Low Data Value Channel 1
Word 14 SGN
Ramp Rate Channel 1
Word 15
NU
Word 16
EC
NU
EHI ELI
LC
ER FM PM NU PFE
Word 17
NU
Format Ch2
NU
Type/Range Sel Ch2
Word 18
SGN
Fault Value Channel 2
Word 19
SGN
Program (Idle) Value Channel 2
Word 20 SGN
Clamp High Data Value Channel 2
Word 21 SGN
Clamp Low Data Value Channel 2
Word 22 SGN
Ramp Rate Channel 2
Word 23
NU
Word 24
EC
NU
EHI ELI
LC
ER FM PM NU PFE
Word 25
NU
Format Ch3
NU
Type/Range Sel Ch3
Word 26
SGN
Fault Value Channel 3
Word 27
SGN
Program (Idle) Value Channel 3
Word 28 SGN
Clamp High Data Value Channel 3
Word 29 SGN
Clamp Low Data Value Channel 3
Word 30 SGN
Ramp Rate Channel 3
Word 31
NU