Measuring Cable Length (LENGTH)

1788-UM002A-US-P – April 2000

4. Press

E

to check the cable selection.

The MediaChecker displays the cable selection for a
few seconds and then starts the test. If the cable
selection is not correct, refer to “Preparing the
MediaChecker for Use” on page 8 to select a new
cable setting. “CAL” appears in the second line of the
display if a cable calibration has been performed for
the selected cable type.

Important: When a length measurement flashes on the

display, the length of the cable exceeds
either the maximum allowed by the standard
(for DeviceNet, DH+/RIO, and Ethernet
cables) or the MediaChecker’s range of
measurement (for ControlNet cables).

The information displayed depends on the type of cable
selected.

For a DeviceNet cable with no failures, the display shows
the following:

aan11f.eps

The MediaChecker cannot determine the length of a
coaxial cable terminated with a resistance. Only the total
resistance of the wire and the terminator is displayed. An
unterminated coaxial cable 445 ft long gives the following
result: