Rockwell Automation 1788 NetLinx Media Checker Users Manual User Manual

Page 42

Advertising
background image

42

Specifications

1788-UM002A-US-P – April 2000

Table 18. ControlNet Cable Test Specifications

Cable Length

Distance to Short

Cable

1

Range

Accuracy

Resolution

2

Accuracy

Resolution

2

ControlNet RG-6
ControlNet RG-6F (high flex RG-6)
ControlNet DS3/4 5065

1 m to 650 m

(2 ft to 2130 ft)

10 % + 1 m (6 ft)

0.5 m (1 ft)

10 % + 10 m

(10 % + 30 ft)

1 m (5 ft)

1. For these cable types, the length to an open is displayed, but the “OPEN” error message is not displayed.

2. 0.5 m (1 ft) for cables <100 m long (328 ft); 1 m (5 ft) for cables >100 m long; 1 ft (0.5 m) for cables to 999 ft long (305 m); 10 ft for

cables > 999 ft long.

Table 19. DeviceNet Cable Test Specifications

Cable Length

Distance to Short

Cable

1

Range

2

Accuracy

Resolution

Accuracy

2

Resolution

3

DeviceNet Thick

1 m to 500 m (3 ft to 1640 ft)

DeviceNet KwikLink

1 m to 420 m (3 ft to 1380 ft)

10 % + 12 m (40 ft)

1 m (5 ft)

DeviceNet Thin

1 m to 100 m (3 ft to 328 ft)

7 % + 2 m (6 ft)

See Note 3

7 % + 3 m (10 ft)

0.5 m (1 ft)

1. For these cable types, the length to an open is displayed, but the “OPEN” error message is not displayed.

2. For the data pair only. Lengths greater than 999 ft are rounded to the nearest 10 ft.

3. 0.5 m (1 ft) for cables <100 m long (328 ft); 1 m (5 ft) for cables >100 m long; 1 ft (0.5 m) for cables to 999 ft long (305 m); 10 ft (3 m)

for cables >999 ft long.