Minimum space, Panel mount, Minimum space panel mount – Rockwell Automation 1769-ASCII Compact I/O ASCII Module User Manual

Page 15

Advertising
background image

Rockwell Automation Publication 1769-UM012B-EN-P - January 2014

15

Compact I/O ASCII Module

Chapter 1

9. Lock the end-cap bus terminator (6).

Minimum Space

Maintain spacing, for example, from enclosure walls, wireways, adjacent
equipment. Allow 50 mm (2 in) of space on all sides for adequate ventilation.

Panel Mount

Mount the module to a panel by using two screws per module. Use M4 or #8
panhead screws. Mounting screws are required on every module.

Panel Mount Procedure with the Dimensional Template

IMPORTANT

You must use a 1769-ECR or 1769-ECL right- or left-end cap to terminate
the end of the serial communication bus.

ATTENTION: During panel or DIN rail mounting of all devices, be sure that all
debris (for example, metal chips and wire strands) is kept from falling into the
module. Debris that falls into the module could cause damage on powerup.

Controller

Compact I/O

Compact I/O

Compact I/O

Compact I/O

Compact I/O

End Cap

Top

Bottom

Side

Side

Host Controller

Compact I/O

Compact I/O

Compact I/O

Right End Cap

All dimensions

are in mm (inches). Hole
spacing tolerance:
±0.4 mm (0.016 in.)

For more than 2 modules: ( number of modules - 1) X 35 mm (1.38 in.)

Refer to host controller documentationfor this dimension.

132

(5.197)

122.6±0.2

(4.826±0.008)

35

(1.38)

28.5

(1.12)

Advertising