Rockwell Automation Publication 1769-UM012B-EN-P - January 2014

93

Configure the 1769-ASCII Module as a Generic Module

Appendix A

transfer from input to output

10. Download your program to the controller.
11. Place the controller in Run mode.
12. Connect channel 0 of the ASCII module to a COM port of your

computer.

13. Run HyperTerminal.
14. Configure HyperTerminal so that the configuration matches the ASCII

device for baud rate and framing.

15. Turn off flow control.
16. In HyperTerminal, type in a value.

Type some text into HyperTerminal. When you press enter, the ASCII
module returns the same line of text back to your screen.

TIP

For a detailed example, see the 1769-ASCII module example in RSLogix
5000 software, version 15, called Example_for_1769-_ASCII_Module.ACD
at \RSLogix 5000\Projects\Samples\ENU\v15\Rockwell Automation.