Appendix a, Appendix – Rockwell Automation 1769-ASCII Compact I/O ASCII Module User Manual

Page 87

Advertising
background image

Rockwell Automation Publication 1769-UM012B-EN-P - January 2014

87

Appendix

A

Configure the 1769-ASCII Module as a Generic
Module

This example demonstrates a CompactLogix program using channel 0 of the
ASCII module to collect a line of input from HyperTerminal and echo that line
back to you.

For information on the MicroLogix controller, see

Configure the Module for Use

with a MicroLogix Controller on page 57

.

Use the following quick start to make sure your ASCII module is functioning
properly.

1. Open Logix Designer software.
2. Create a new project.

In this example, the name of the project is L35 CR_Quickstart_001.

3. Create a 1769-MODULE (generic) in the I/O configuration.
4. When the I/O module properties appear, enter the following information:

a name, the appropriate slot number, specify a Comm Format of
Data_INT, and enter the following values:

5. Press OK.

Assembly Instance

Size

Input

101

108

Output

100

108

Configuration

102

31