Rockwell Automation Publication 1769-UM012B-EN-P - January 2014

Chapter 3

I/O Memory Mapping

Channel 1

Module Properties Dialog Box 16

Serial Character Framing

0…8

0 = 7N2, 1 = 7E1, 2 = 7O1, 3 = 8N1, 4 = 8N2, 5 = 8E1,
6 = 8O1, 7 = 7E2, 8 = 7O2

CH1BaudRate

17

Serial Port Speed

0…7

0 = 9600, 1 = 1200, 2 = 2400, 3 = 4800, 4 = 19200,
5 = 38400, 6 = 57.6k, 7 = 115.2k (half-duplex only)

Serial Port Receive Data

Module Properties Dialog Box 18

Max Number of Receive Characters

0…200

In Simultaneous mode, the total number of channel 0 characters plus
channel 1 characters cannot exceed 200.

Ch1RxStartMode

19

Receive Record Start Mode

0…2

0 = ignore, 1 = exclude, 2 = include start delimiter

Ch1RxStartDelimiter

20

Receive Start Delimiter

(1)

0…127/255

0…0x7f (0…127) for 7-bit data
0…0xff (0…255) for 8-bit data

Ch1RxEndMode

21

Receive Record End Mode

0…2

0 = ignore, 1 = exclude, 2 = include end delimiter

Ch1RxEndDelimiter

22

Receive End Delimiter

(1)

0…127/255

0…0x7f (0…127) for 7-bit data
0…0xff (0…255) for 8-bit data

Module Production Data

Ch1RxPadChar

23

Pad Character

(1)

0…127/255

0…0x7f (0…127) for 7-bit data
0…0xff (0…255) for 8-bit data

Ch1RxByteSwapMode

24

Receive Swap Mode

0…2

0 = disabled, 1 = 16-bit, 2 = 32-bit

Ch1RxByteHandshakeMode

25

Master Handshake Mode

0…1

0 = master/slave handshake, 1 = produce immediate

CH1RxMessageTimeout

26

Message Time Out

0…65535

0 = none, 1 to 65535 ms

Serial Port Transmit Data

Module Properties Dialog Box 27

Max Number of Transmit Characters

0…200

In Simultaneous mode, the total number of channel 0 characters plus
channel 1 characters cannot exceed 200.

Ch1TxEndMode

28

Transmit Record End Mode

0…2

0 = ignore, 1 = exclude, 2 = include end delimiter

Ch1TxEndDelimiter

29

Transmit End Delimiter

(1)

0…127/255

0…0x7f (0…127) for 7-bit data
0…0xff (0…255) for 8-bit data

Ch1TxByteSwapMode

30

Transmit Swap Mode

0…2

0 = disabled, 1 = 16-bit, 2 = 32-bit

(1) To enter values 128…255, use this conversion formula: Desired Decimal Value - 256 = Entered Decimal Value. For example, for an ASCII character value of 128, 128 - 256 = -128.

Table 9 - Configuration File Tag Names (Continued)

Tag Definition

Wo

rd

Description

Values

Valid Data Values