Rockwell Automation 1769-ASCII Compact I/O ASCII Module User Manual
Page 88
Advertising
88
Rockwell Automation Publication 1769-UM012B-EN-P - January 2014
Appendix A
Configure the 1769-ASCII Module as a Generic Module
6. Open the controller tags for monitor to enter the following configuration
parameters in the Local:<slot>:C tag data members.
All other parameters are 0.
This is a controller-scoped configuration tag.
Data [ ] Word
Value (Decimal)
Meaning
0
0
Alternating mode
1
3
Framing is 8N1
2
0
9600 baud
3
80
Max Rx Characters
6
1
Use an Rx End delimiter, but exclude it from the input buffer
7
13
Use a Carriage Return as the Rx End delimiter
10
1
Produce data when available
12
80
Max Tx Characters