Wiring differential inputs – Rockwell Automation 1769-IF4I CompactLogix Isolated Analog Input Module User Manual

Page 11

Advertising
background image

CompactLogix Isolated Analog Input Module 11

Publication 1769-IN074C-EN-P - March 2011

Voltages on Ch+, Ch-, and Ch_iRtn for a single, isolated channel of the 1769-IF4I
module must not exceed the maximum overload levels detailed in the

Input Specifications on page 21

.

Wiring Differential Inputs

ATTENTION: To comply with UL restrictions, this equipment must be powered
from a source compliant with Class 2 or Limited Voltage/Current.

Be careful when stripping wires. Wire fragments that fall into a module could
cause damage at power up. Once wiring is complete, make sure that the module
is free of all metal fragments.

IMPORTANT

1769-IF4I input channels connected to current sources must have a jumper wire
placed between Ch#_iRtn and the Ch#- terminals for that channel.

Belden 8761 Cable
(or Equivalent)

Analog Source

Advertising