CompactLogix Isolated Analog Input Module 17

Publication 1769-IN074C-EN-P - March 2011

The bits are defined as follows:

EC = Enable Channel

Inpt Dta Fm Chlx = Input Data Format Select

EA = Enable Alarm

AL = Alarm Latch

EI = Enable Interrupt

(1)

Inpt Tp/Rnge Sel Chlx = Input Type/Range Select

Inpt Filter Sel Chlx = Input Filter Select

Reserved = Allows for future expansion

ETS = Enable Time Stamp

24

S

Alarm Dead Band Value Channel 3

25

Reserved

(1)

MicroLogix 1500 and CompactLogix L3x controllers do not support interrupts.

Bit Definitions for Channel Configuration Words

Define

To Select

Make these bit settings

15

14

…11 10 9

8

7

…4 3

2

1

0

Input Filter Selection

60 Hz

0

0

0

0

50 Hz

0

0

0

1

28.5 Hz

0

0

1

0

300 Hz

0

0

1

1

360 Hz

0

1

0

0

Enable Interrupt

Enable

1

Disable

0

Enable Process
AlarmLatch

Enable

1

Disable

0

Enable Process
Alarms

Enable

1

Disable

0

Enable Channel

Enable

1

Disable

0

Configuration Data Array (cont.)

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0