20 CompactLogix Isolated Analog Input Module

Publication 1769-IN074C-EN-P - March 2011

Surge transient immunity

IEC 61000-4-5

±1 kV line-earth(CM) on shielded ports

Conducted RF immunity

IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150
kHz…80 MHz

Supply power and current ratings

Backplane:

•

5V DC, 140 mA

•

24V DC, 110 mA

Voltage Inputs:

•

±10V DC

•

0…10V DC

•

1…5V DC

•

0…5V DC (30V DC max)

Current Inputs:

•

0…20 mA

•

4…20 mA

Isolation voltage

30V (continuous), reinforced insulation type,
channel to system and channel to channel

Type tested at 710V DC for 60 s

Environmental Specifications 1769-IF4I