20 CompactLogix Isolated Analog Input Module
Publication 1769-IN074C-EN-P - March 2011
Surge transient immunity
IEC 61000-4-5
±1 kV line-earth(CM) on shielded ports
Conducted RF immunity
IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150
kHz…80 MHz
Supply power and current ratings
Backplane:
•
5V DC, 140 mA
•
24V DC, 110 mA
Voltage Inputs:
•
±10V DC
•
0…10V DC
•
1…5V DC
•
0…5V DC (30V DC max)
Current Inputs:
•
0…20 mA
•
4…20 mA
Isolation voltage
30V (continuous), reinforced insulation type,
channel to system and channel to channel
Type tested at 710V DC for 60 s
Environmental Specifications 1769-IF4I